SPPA T2000 S5 communication with S7 AP SINEC H1

Configuring SPPA T2000 site

1. In topology diagram (YDH) , create auxilary system S5 (even actualy S7 AP) with CP1430
2. Configure "Head End" AS620B-S5 auxilary connection to S5
3. Generate LAN
4. You will get :
- MAC ADDRESS for Simatic S5 auxilary (actualyy S7 CPU)
- TSAP connection
- DB Send/Receive and lenght (normally 512 byte)


Configuring S7 CPU site
1. Configure S7 system (CPU, CP443-1, Power supply, ETC)
2. Using Netpro, create S5 CPU with ISO connection send/receive protocol
3. Set MAC Address of S5 CPU (actually AS620B-S5 Head end CPU) that generated by ES680
4. Set TSAP to S5 CPU that gerated by ES680
5. Set MAC and TSAP Address on CP443-1 simatic S7 that generated by ES680 (from Teleperm XP site, the S7 shown and configured as S5 auxiliary)
6. Insert APRED S7 Function block FB1, FB2, FB3 to S7 CPU
7. Configure APPRED parameter base on Conn ID of CP 443-1, DB adress Source, DB addres target e.t.c (see APRED S7 Manual)
8. Download CPU S7
9. Online CP443-1 diagnostic/module information, ensure ISO connection establish
10. test data transfer on DB sources/Target

Comments